Electronic Hygrotherm
ETF 012

  • Temperature and humidity adjustable
  • Wide voltage range
  • Operating temperature down to -40°C
  • High switching capacity
  • Status indicator (LED)

The electronic hygrotherm senses the ambient temperature and relative humidity in an enclosure with electric/electronic components and turns on a heater (or alternatively a fan) at either set point, helping prevent the formation of condensation in the enclosure. Due to its wide voltage range the hygrotherm can be utilised anywhere in the world. The LED integrated in the adjustment knob on the active controller is lit when the connected device is in operation.

Switch difference (temperature)2K (±1K tolerance) at +25°C (+77°F), 50% RH
Switch difference (humidity)4% RH (±1% tolerance) at +25°C (+77°F), 50% RH
Reaction time (humidity)approx. 5 sec.
Contact typechange-over contact (relay)
Service lifeVDE: NO/NC > 15,000 cycles
UL: NO/NC > 30,000 cycles
Max. switching capacity (relay output)240VAC, 10 (1.6) A
60VDC, 0.6A¹
Max. inrush currentAC 30A for 10 sec.
Optical indicatorLED
Connection5-pole terminal, clamping torque 0.5Nm max.:
rigid/stranded² wire 2.5mm² (AWG 14)
Mountingclip for 35mm DIN rail, EN 60715
Casingplastic according to UL94 V-0, light grey
Dimensions77 x 60 x 43mm
Weightapprox. 0.2kg
Fitting positionvertical
Operating/Storage temperature-40 to +60°C (-40 to +140°F)
Operating/Storage humiditymax. 90% RH (non-condensing)
Protection typeIP20
ApprovalsVDE, UL File No. E164102, EAC

¹ not UL confirmed

To top

² When connecting with stranded wires, wire end ferrules must be used.

Art. No.Operating voltageSetting range temperatureSetting range humidity
01230.0-00100-240VAC, 50/60Hz (min. 90VAC, max. 265VAC)0 to +60°C50 to 90% RH
01230.9-00100-240VAC, 50/60Hz (min. 90VAC, max. 265VAC)+32 to +140°F50 to 90% RH
01230.1-0024-48VDC (min. 20VDC, max. 60VDC)0 to +60°C50 to 90% RH

To top

Technical Drawing

Electronic Hygrotherm ETF 012

To top